I am happy to announce release of SW user module for Conel routers, which adds 3G DNP3 outstation details functionality. Module been tested with ClearSCADA before public release.
DNP3 profile and additional documentation and SW user module can be downloaded in our download section. I mentioned the work on 3G DNP3 outstation here as well.
**Prerequisite: **
- Router need to have firmware 3.0.8 or higher
- For GPS values - GPS user module needs to be loaded and started, available on selected router models
All values are accessible via Class 1 read.
Data are listed in following order:
Binary inputs:
Index | Input |
0 | Binary input - build in (excludes Libratum series) |
1 | BIN1 XC-CNT board (position - Port1) |
2 | BIN2 XC-CNT board (position - Port1) |
3 | BIN3 XC-CNT board (position - Port1) |
4 | BIN4 XC-CNT board (position - Port1) |
5 | BIN1 XC-CNT board (position - Port2) |
6 | BIN2 XC-CNT board (position - Port2) |
7 | BIN3 XC-CNT board (position - Port2) |
8 | BIN4 XC-CNT board (position - Port2) |
Analog values:
Index | Value |
0 | AN1 XC-CNT board (position - Port1) |
1 | AN2 XC-CNT board (position - Port1) |
2 | AN1 XC-CNT board (position - Port2) |
3 | AN2 XC-CNT board (position - Port2) |
4 | Input voltage - value needs to be scaled by 1000 (value/1000) |
5 | Router temperature in °C |
6 | Signal strength |
7 | GPS Latitude in degrees - value needs to be scaled by 1000000 (value/10000000) |
8 | GPS Longitude in degrees - value needs to be scaled by 1000000 (value/10000000) |
Note: For GPS data to be available, GPS SW user module needs to be loaded and running (available only with GPS hardware supported models).
Binary output
Index | Value |
0 | Counter value CNT1 XC-CNT board (position - Port1) |
1 | Counter value CNT2 XC-CNT board (position - Port1) |
2 | Counter value CNT1 XC-CNT board (position - Port2) |
3 | Counter value CNT2 XC-CNT board (position - Port2) |
4 | Rx Data WLAN interface - Bytes |
5 | Tx Data WLAN interface - Bytes |
6 | Uptime - minutes |
7 | Serial number or the router |
Index | Output |
0 | binary output - build in (excludes Libratum series) |
1 | binary output OUT1 XC-CNT board (position - Port1) |
2 | binary output OUT1 XC-CNT board (position - Port2) |
Support for read and set for time.
You can configure TCP/UDP connection parameters and address of the master and outstation via web interface of the user module.